BURKERT控制器1150系列技術(shù)參數(shù):
Controller structure  | P, I, PD, PI, PID  | PID  | Control loop feedback  | |
Proportional band  | 0  | to 9999 digits  | 0 digits  | Size of the proportional band  | 
  | 
  | 
  | 
  | 0 means that the controller structure is out of action!  | 
Derivative time  | 0  | to 9999 sec  | 80 sec  | Determines the differential component of the controller output signal  | 
Reset time  | 0  | to 9999 sec  | 350 sec  | Determines the integral component of the controller output signal  | 
Cycle time  | 0  | to 9999 sec  | 20 sec  | When using a switched output, the cycle time should be chosen so  | 
  | 
  | 
  | 
  | that the energy fl ow to the process is quasi continuous, i.e. as con-  | 
  | 
  | 
  | 
  | tinuous as is practicable without overloading the switching elements  | 
Contact spacing  | 0  | to 999 sec  | 0 digits  | The spacing between the two controller contacts for double-  | 
  | 
  | 
  | 
  | setpoint or modulating controllers, or proportional controllers  | 
  | 
  | 
  | 
  | with an integrated actuator driver  | 
Switching differential  | 0  | to 999 digits  | 1 digits  | Hysteresis for switching controllers with proportional band = 0  | 
Actuator time  | 5  | to 3000 sec  | 60 sec  | The actually utilized operating time of the regulator valve with  | 
  | 
  | 
  | 
  | modulating controllers or proportional controllers with an integrated  | 
  | 
  | 
  | 
  | actuator driver  | 
Working point  | -100  | to +100%  | 0%  | The output level for P and PD controllers (if x = w then y = Y0)  | 
Output level limiting  | 0  | to 100%  | 100%  | The maximum limit for the output level  | 
  | -100  | to +100%  | -100%  | The minimum limit for the output level  | 
Minimum relay ON time  | 0  | to 60 sec  | 0 sec  | Limits the frequency of switching for switched outputs  | 